๐Ÿ“ How Far Can You Run 12 Gauge Wire?

Real distance limits for every common gauge โ€” and why every site gives you a different number.

The short answer

On a fully loaded 20 amp, 120 V circuit, #12 copper stays under the 3% voltage-drop target for about 46 one-way feet. At 240 V the same wire goes about 91 feet. Lighter actual loads go further โ€” a 20 A breaker feeding a 10 A load doubles the distance. Full table below; your exact case: Max Wire Length calculator.

Distance table (3% drop, copper, fully loaded)

WireAt ampsMax one-way @120 VMax one-way @240 V
14 AWG15 A38 ft76 ft
12 AWG15 A61 ft121 ft
12 AWG20 A46 ft91 ft
10 AWG30 A48 ft97 ft
8 AWG40 A58 ft115 ft
6 AWG50 A73 ft146 ft

Computed with our verified engine (K = 12.9 ohmยทcmil/ft for copper). Distances are one-way โ€” from panel to load; the round trip is already accounted for.

Why other sites say 50, 57, or 100 feet

Three honest reasons, no conspiracy. First โ€” the amps assumption. Should you compute at the breaker's 20 A or the actual load's amps? Forums split 50/50 on this. Our table uses the breaker rating (worst case, safe for planning); if you know the real load, use it in the calculator and enjoy the extra distance. Second โ€” the resistance constant. We use the field-standard K = 12.9, which is deliberately a bit conservative; some sites use the code's DC resistance table, which yields ~25% longer distances (that's the famous "57 feet"). Neither is wrong โ€” ours leaves margin for real-world conditions. Third โ€” the target. 3% is the common planning target, but it's a recommendation, not a hard law (full story here) โ€” sites using 5% quote much longer runs.

What happens if you run too far?

Nothing dramatic โ€” and that's the trap. The circuit works, but the far end runs at lower voltage: motors start hard and run hot (a compressor that trips on a 100 ft extension cord but not a short one is pure voltage drop), LEDs flicker, chargers slow down, heaters underperform. Long runs also waste real energy as heat in the wall.

Worked example

#12 copper, 20 A, 80 one-way feet, 120 V: drop = 2 ร— 12.9 ร— 20 ร— 80 รท 6,530 = 6.3 V = 5.3% โ€” over both the 3% target and the 5% outer limit. Options: shorten the run, go up to #10 (drops 4.0 V = 3.3%), run it at 240 V if the load allows, or accept it for a non-critical load. The Voltage Drop calculator shows all of this instantly.

Related

Max Wire Length calculator ยท Voltage drop, explained ยท Ampacity chart