🔥 Wire Ampacity Chart (NEC Table 310.16)

The full copper and aluminum table — current code — plus the one thing everyone gets wrong: which temperature column you're allowed to use.

The chart

Amps each wire can carry continuously (up to three current-carrying wires in a cable or conduit, ordinary room temperature). These values are identical in the 2017, 2020, and 2023 NEC editions — we verified that against the published tables, so this chart is current by construction:

SizeCopperAluminum
60°C75°C90°C60°C75°C90°C
14 AWG152025
12 AWG202530152025
10 AWG303540253035
8 AWG405055354045
6 AWG556575405055
4 AWG708595556575
3 AWG85100115657585
2 AWG951151307590100
1 AWG11013014585100115
1/0125150170100120135
2/0145175195115135150
3/0165200225130155175
4/0195230260150180205
250 kcmil215255290170205230
300 kcmil240285320195230260
350 kcmil260310350210250280
400 kcmil280335380225270305
500 kcmil320380430260310350

Source-verified against two verbatim NEC table reproductions. Small-conductor breaker caps (NEC 240.4(D)) still apply: 14 Cu → 15 A breaker, 12 Cu → 20 A, 10 Cu → 30 A, 12 Al → 15 A, 10 Al → 25 A, regardless of column. Interactive version with the caps built in: Ampacity Check.

Which column am I allowed to use?

This is the single most-argued ampacity question on every electrician forum, and the rule is simpler than the arguments: use the column of your weakest link. The wire's insulation has a rating (THHN is 90°C), but the breaker lugs and receptacle terminals it lands on are usually rated 75°C — and Romex/NM-B cable is capped at the 60°C column by code no matter what its conductors say. So in practice: NM-B → 60°C column. THHN in conduit on standard equipment → 75°C column. The 90°C column is mostly useful as the starting point for derating calculations (hot attics, bundled cables), not as a rating you deliver to a breaker.

Does voltage change ampacity?

No — and this surprises a lot of the 12-volt crowd. A #10 wire can carry the same ~30 A whether it's a 12 V trolling-motor feed or a 240 V circuit. What changes brutally with voltage is voltage drop: losing 3 volts means losing 1.3% of a 240 V circuit but a crushing 25% of a 12 V one. That's why low-voltage wiring runs so much fatter than its amps suggest — check yours in the Voltage Drop calculator (it has a DC mode for exactly this).

What this chart doesn't cover

Normal conditions only: hot environments, more than three current-carrying conductors bundled together, and continuous loads (3+ hours → 80% rule) all reduce these numbers. A derating upgrade to our Ampacity tool is on the roadmap.