๐ What Size Wire for a 30 Amp Breaker?
The short answer
Start with 10 AWG copper for an ordinary 30 A circuit. A TT-30 RV receptacle is 120 V, while a typical dryer or water-heater circuit is 240 V; that voltage difference changes long-run sizing.
The verified ampacity table supports #8 aluminum at 30 A under ordinary 75ยฐC termination conditions, so aluminum is included. Confirm the conductor type, terminals, and equipment listing before using it. Ampacity Check tool.
Distance changes the answer
Minimum size at the full 30 A and at or under 3% voltage drop. Distance is one way; the calculator also rejects any size that fails ampacity.
30 A at 240 V โ dryer or water heater
| Material | 50 ft | 100 ft | 150 ft | 200 ft | 250 ft |
|---|---|---|---|---|---|
| Copper | 10 | 8 | 8 | 6 | 4 |
| Aluminum | 8 | 6 | 4 | 4 | 3 |
30 A at 120 V โ RV TT-30
| Material | 50 ft | 100 ft | 150 ft | 200 ft | 250 ft |
|---|---|---|---|---|---|
| Copper | 8 | 6 | 4 | 3 | 2 |
| Aluminum | 6 | 4 | 2 | 1 | 1/0 |
Common 30-amp jobs
Dryers, water heaters, RV receptacles, and some mini-split or air-conditioning circuits commonly land near this rating. Use the equipment nameplate when it gives a different circuit requirement.
Worked example: 30 A RV receptacle at 100 feet
At 120 V, our verified calculator selects #6 copper (26,240 circular mils): 2 ร 12.9 ร 30 ร 100 รท 26,240 = 2.95 V, or 2.46%. The 240 V table is smaller because the same volts lost are half the percentage.
Related
30-amp wire size FAQ
- What size wire for a 30 amp RV plug?
- A TT-30 RV receptacle is 120 V. Start with 10 AWG copper at ordinary distances, then use the 120 V table or calculator for the actual one-way run.
- Can 12 gauge wire handle 30 amps?
- No. NEC 240.4(D) caps 12 AWG copper at 20 A for ordinary circuits, so it does not pass a 30 A ampacity check.
- What size wire does a 30 amp dryer use?
- Start with 10 AWG copper for an ordinary 30 A dryer circuit. Check the appliance instructions, cable type, and distance before installation.