๐Ÿ”Œ What Size Wire for a 30 Amp Breaker in Canada?

๐Ÿ‡บ๐Ÿ‡ธ US version

The short answer

Start with 10 AWG copper NMD90 for an ordinary 30 A circuit. A TT-30 RV receptacle is 120 V, while a typical dryer or water-heater circuit is 240 V; that voltage difference changes long-run sizing.

The verified 60ยฐC column supports #8 aluminum at 35 A, so aluminum is included. Confirm the conductor type, terminals, and equipment listing in the Canadian Ampacity Check tool. Ampacity Check tool.

Distance changes the answer โ€” and Rule 8-102 is mandatory

Minimum size at the full 30 A and at or under the mandatory 3% voltage-drop limit. Distance is one way; the calculator also rejects any size that fails ampacity.

30 A at 240 V โ€” dryer or water heater

Material15 m (50โ€ฒ)30 m (100โ€ฒ)46 m (150โ€ฒ)61 m (200โ€ฒ)76 m (250โ€ฒ)
Copper108864
Aluminum86443

30 A at 120 V โ€” RV TT-30

Material15 m (50โ€ฒ)30 m (100โ€ฒ)46 m (150โ€ฒ)61 m (200โ€ฒ)76 m (250โ€ฒ)
Copper86432
Aluminum64211/0

Wire Size calculator

Common Canadian 30-amp jobs

Dryers, water heaters, RV park receptacles, baseboard heat, and some mini-split circuits commonly land near this rating. Use the equipment nameplate when it gives a different circuit requirement.

Worked example: 30 A RV receptacle at 30 m (100 ft)

At 120 V, our verified calculator selects #6 copper (26,240 circular mils): 2 ร— 12.9 ร— 30 ร— 100 รท 26,240 = 2.95 V, or 2.46%. The 240 V table is smaller because the same volts lost are half the percentage.

Related

Wire Size calculator ยท Ampacity Check tool

30-amp wire size FAQ

What size wire for a 30 amp RV plug in Canada?
A TT-30 RV receptacle is 120 V. Start with 10 AWG copper NMD90 at ordinary distances, then use the 120 V table or calculator for the actual one-way run.
Can 12 gauge wire handle 30 amps in Canada?
No. CEC Rule 14-104 caps 12 AWG copper at a 20 A overcurrent device for ordinary circuits, so it does not pass a 30 A ampacity check.
What size wire does a 30 amp dryer use in Canada?
Start with 10 AWG copper NMD90 for an ordinary 30 A dryer circuit. Check the appliance instructions, termination rule, and distance before installation.