๐ What Size Wire for a 20 Amp Circuit?
The short answer
The everyday answer is 12 AWG copper. Do not put 14 AWG copper on a 20 A breaker for an ordinary branch circuit.
NEC 240.4(D) caps 14 AWG copper at 15 A and 12 AWG copper at 20 A for ordinary circuits. A larger raw ampacity in another temperature column does not erase that cap. Ampacity Check tool.
Distance changes the answer
Minimum copper size at 120 V, sized at the full 20 A and kept at or under the 3% voltage-drop target (one-way distance):
20 A at 120 V
| Material | 50 ft | 100 ft | 150 ft | 200 ft | 250 ft | 300 ft |
|---|---|---|---|---|---|---|
| Copper | 10 | 8 | 6 | 4 | 4 | 3 |
Small-gauge aluminum branch-circuit wire is not shown. Use copper here; check any other wiring method in the Ampacity Check tool. Wire Size calculator.
Common 20-amp jobs
Kitchen small-appliance circuits, bathrooms, garage receptacles, and general lighting are common 20 A jobs. The appliance instructions and local rules still control the final design.
Worked example: 20 A at 120 V over 100 feet
Our verified calculator selects #8 copper (16,510 circular mils): 2 ร 12.9 ร 20 ร 100 รท 16,510 = 3.13 V, or 2.6% of 120 V. It passes both the ampacity check and the 3% drop target.
Related
How far can you run 12 gauge wire? ยท Wire Size calculator ยท Ampacity Check tool
20-amp wire size FAQ
- Can I use 14 gauge wire on a 20 amp breaker?
- Use 12 AWG copper for an ordinary 20 A branch circuit. NEC 240.4(D) caps 14 AWG copper at 15 A, so it cannot be protected by a 20 A breaker for this ordinary use.
- How far can I run 12 gauge wire on 20 amps?
- 12 AWG is the starting answer, but its useful distance depends on voltage and load. Use the dedicated distance guide or enter the exact run in the Wire Size calculator.
- What about 20 amps at 240 V?
- The ampacity floor stays 12 AWG copper at 20 A, but 240 V gives more voltage-drop room than 120 V. Enter the actual distance and voltage in the Wire Size calculator.