๐Ÿ“ How Far Can You Run 12 Gauge Wire in Canada?

Distance limits by gauge, in metres and feet โ€” under a code where the limit is mandatory. ๐Ÿ‡บ๐Ÿ‡ธ US version

The short answer

On a fully loaded 20 amp, 120 V circuit, #12 copper stays inside the 3% drop limit for about 14 m (46 ft) one-way; at 240 V, about 28 m (91 ft). And in Canada that 3% is not advice โ€” CEC Rule 8-102 makes it enforceable. The full table is below; your exact case: Max Wire Length calculator.

Distance table (3% drop, copper, fully loaded)

WireAt ampsMax one-way @120 VMax one-way @240 V
14 AWG15 A12 m (38 ft)23 m (76 ft)
12 AWG15 A19 m (61 ft)37 m (121 ft)
12 AWG20 A14 m (46 ft)28 m (91 ft)
10 AWG30 A15 m (48 ft)30 m (97 ft)
8 AWG40 A18 m (58 ft)35 m (115 ft)
6 AWG50 A22 m (73 ft)45 m (146 ft)

Computed with our verified engine (K = 12.9 for copper). Distances are one-way; the round trip is accounted for.

Breaker amps or actual load? Canada actually answers this

The eternal calculator argument โ€” do you compute at the breaker's rating or the load's real draw โ€” has an official Canadian answer: the 2024 CEC says use the connected load if you know it, otherwise 80% of the breaker rating. Our table uses 100% of the breaker (extra margin); at the CEC's 80% basis, every distance above stretches 25% further โ€” so a #12/20 A circuit reaches about 18 m (57 ft) at 120 V. Either way you land inside the rule; ours just lands with room to spare. The calculator takes whichever amps you give it.

Special Canadian case: houses get a lookup table

For ordinary lighting and receptacle circuits in dwellings (up to 20 A, 120 V), the CEC even publishes precomputed maximum lengths (Rule 8-102(3) with Table 68) so electricians don't have to calculate at all โ€” with a bonus: if the run from the service to your panel is short (under 20 m), the branch circuit may use the whole 5% budget itself. Dedicated circuits โ€” fridge, kitchen, heating โ€” don't get that shortcut and use the standard calculation, which is exactly what our tools do.

What happens if you run too far?

Physics doesn't care about borders: motors start hard and run hot, LEDs flicker, chargers crawl, and energy turns into heat in the wall. The Canadian difference is bureaucratic โ€” an over-limit run can also fail inspection, since 8-102 is enforceable.

Worked example

#12 copper, 20 A, 24 m (80 ft) one-way, 120 V: drop = 2 ร— 12.9 ร— 20 ร— 80 รท 6,530 = 6.3 V = 5.3% โ€” over the mandatory limit. Fixes: #10 wire (3.3%), a 240 V configuration if the load allows, or a shorter route. The Voltage Drop calculator shows the options instantly.