🧮 导管填充对照表(CEC)
简短答案
按 CEC Rule 12-910 和 Table 8,同一规格的 RW90 导体在一根导管里能穿多少根。各列是公制标号:16 为 ½ 英寸,21 为 ¾ 英寸,27 为 1 英寸。
EMT
| 导体规格(RW90) | 16 | 21 | 27 | 35 | 41 | 53 | 63 | 78 | 91 | 103 | 129 | 155 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 14 AWG | 8 | 14 | 24 | 42 | 58 | 96 | 170 | 200 | 200 | 200 | 200 | 200 |
| 12 AWG | 6 | 11 | 18 | 32 | 44 | 73 | 130 | 196 | 200 | 200 | 200 | 200 |
| 10 AWG | 4 | 8 | 13 | 23 | 32 | 54 | 96 | 145 | 189 | 200 | 200 | 200 |
| 8 AWG | 2 | 4 | 7 | 13 | 18 | 30 | 53 | 80 | 105 | 134 | 185 | 200 |
| 6 AWG | 1 | 3 | 5 | 9 | 13 | 22 | 39 | 60 | 78 | 100 | 137 | 198 |
| 4 AWG | 1 | 2 | 4 | 7 | 9 | 16 | 28 | 43 | 56 | 72 | 99 | 143 |
| 3 AWG | 1 | 2 | 3 | 6 | 8 | 13 | 24 | 36 | 48 | 61 | 84 | 121 |
| 2 AWG | 1 | 1 | 2 | 5 | 6 | 11 | 20 | 30 | 40 | 51 | 70 | 101 |
| 1 AWG | 0 | 1 | 2 | 3 | 5 | 8 | 15 | 23 | 30 | 38 | 52 | 75 |
| 1/0 AWG | 0 | 1 | 1 | 3 | 4 | 7 | 12 | 19 | 25 | 31 | 43 | 63 |
| 2/0 AWG | 0 | 0 | 1 | 2 | 3 | 6 | 10 | 16 | 20 | 26 | 36 | 53 |
| 3/0 AWG | 0 | 0 | 1 | 2 | 3 | 4 | 8 | 13 | 17 | 22 | 30 | 44 |
| 4/0 AWG | 0 | 0 | 1 | 1 | 2 | 4 | 7 | 11 | 14 | 18 | 25 | 36 |
| 250 kcmil | 0 | 0 | 0 | 1 | 2 | 3 | 6 | 9 | 11 | 15 | 20 | 29 |
| 300 kcmil | 0 | 0 | 0 | 1 | 1 | 2 | 5 | 7 | 10 | 12 | 17 | 25 |
| 350 kcmil | 0 | 0 | 0 | 1 | 1 | 2 | 4 | 6 | 8 | 11 | 15 | 22 |
| 400 kcmil | 0 | 0 | 0 | 1 | 1 | 2 | 4 | 6 | 7 | 10 | 13 | 20 |
| 450 kcmil | 0 | 0 | 0 | 0 | 1 | 2 | 3 | 5 | 7 | 9 | 12 | 18 |
硬质 PVC
| 导体规格(RW90) | 16 | 21 | 27 | 35 | 41 | 53 | 63 | 78 | 91 | 103 | 129 | 155 | 200 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 14 AWG | 7 | 13 | 22 | 35 | 51 | 91 | 133 | 200 | 200 | 200 | 200 | 200 | 200 |
| 12 AWG | 5 | 10 | 17 | 27 | 39 | 69 | 101 | 157 | 200 | 200 | 200 | 200 | 200 |
| 10 AWG | 4 | 7 | 12 | 20 | 29 | 51 | 75 | 116 | 156 | 200 | 200 | 200 | 200 |
| 8 AWG | 2 | 4 | 7 | 11 | 16 | 28 | 41 | 64 | 87 | 111 | 176 | 200 | 200 |
| 6 AWG | 1 | 3 | 5 | 8 | 12 | 21 | 31 | 48 | 64 | 82 | 130 | 185 | 200 |
| 4 AWG | 1 | 2 | 3 | 6 | 8 | 15 | 22 | 34 | 46 | 59 | 94 | 134 | 200 |
| 3 AWG | 1 | 1 | 3 | 5 | 7 | 13 | 19 | 29 | 39 | 50 | 80 | 113 | 200 |
| 2 AWG | 0 | 1 | 2 | 4 | 6 | 10 | 15 | 24 | 33 | 42 | 67 | 95 | 169 |
| 1 AWG | 0 | 1 | 2 | 3 | 4 | 8 | 11 | 18 | 24 | 31 | 50 | 71 | 126 |
| 1/0 AWG | 0 | 1 | 1 | 2 | 3 | 6 | 9 | 15 | 20 | 26 | 41 | 59 | 104 |
| 2/0 AWG | 0 | 0 | 1 | 2 | 3 | 5 | 8 | 12 | 17 | 22 | 35 | 49 | 87 |
| 3/0 AWG | 0 | 0 | 1 | 1 | 2 | 4 | 6 | 10 | 14 | 18 | 29 | 41 | 73 |
| 4/0 AWG | 0 | 0 | 0 | 1 | 2 | 3 | 5 | 8 | 11 | 15 | 24 | 34 | 60 |
| 250 kcmil | 0 | 0 | 0 | 1 | 1 | 3 | 4 | 7 | 9 | 12 | 19 | 27 | 49 |
| 300 kcmil | 0 | 0 | 0 | 1 | 1 | 2 | 4 | 6 | 8 | 10 | 16 | 24 | 42 |
| 350 kcmil | 0 | 0 | 0 | 0 | 1 | 2 | 3 | 5 | 7 | 9 | 14 | 21 | 37 |
| 400 kcmil | 0 | 0 | 0 | 0 | 1 | 2 | 3 | 4 | 6 | 8 | 13 | 18 | 33 |
| 450 kcmil | 0 | 0 | 0 | 0 | 1 | 1 | 2 | 4 | 5 | 7 | 12 | 17 | 30 |
每个根数都是这样得出的:按 CSA C22.1:24 Tables 9A to 9H 的内径求出导管的内截面积,乘以 Table 8 中对应导体根数的填充限值(一根 53%、两根 31%、三根及以上 40%),再除以 Table 6A 的导体截面积。加拿大不允许进位取整,所以凑不满一整根的就直接不算。 我们如何验证.
仅限同一规格
本表适用于规格完全相同的导体。同一根导管里混用不同规格时,就要改为把实际面积加起来——计算器可以做这件事。 导管填充计算器
改变根数的三个因素
这里列的是 RW90,因为它是常见的带护套建筑用线,也是两者中较粗的,所以这些根数偏保守。T90 更细;计算器里可以选它。
接地跨接导体同样占地方,要计入填充,尽管 Rule 4-004 从不把它计入载流量降容。填充和降容的数法不一样——这一点常把人绕进去。
不论算出来是多少,Rule 12-910(3) 都把任何一根导管限制在 200 根导体以内,所以本表中较大的规格都停在 200。
美国的做法不同
美国的答案不一样:导管不同、导线不同,还允许进位取整,所以美国的根数更大——同一个公制标号 35 导管,也就是加拿大的 1-1/4 英寸,在加拿大只能穿九根 6 AWG RW90,而 NEC 允许在 1-1/4 英寸 EMT 内穿十二根 6 AWG THHN。切勿把任何一个数字跨境照搬。
相关内容
常见问题
- 公制标号 21(¾ 英寸)的导管能穿多少根 12 AWG 导体?
- 公制标号 21 的 EMT 里可穿十一根 12 AWG RW90,硬质 PVC 里是十根。接地跨接导体也要算作其中一根。
- 地线要不要计入导管填充?
- 要算。接地跨接导体计入导管填充。按 Rule 4-004,它从不计入载流量降容——填充和降容的数法不一样。
- 导线规格不一样怎么办?
- 那这张表就不适用了。要把每根导体的实际面积加起来,再和导管的限值比较;进位取整同样不适用。导管填充计算器会替你算。
- 是不是所有情况的限值都是 40%?
- 不是。一根导体可填 53%,两根可填 31%,三根及以上可填 40%。两根的情况最严格,常常出乎人的意料。