🚇 Conduit Fill
How big a conduit do you need for your wires? Enter what you're pulling, get the smallest legal size.
Canadian source: CSA C22.1:24 — Canadian Electrical Code, Part I, 26th edition (2024). This calculator uses conductor areas from Tables 6A/6K, EMT and rigid PVC internal diameters from Tables 9A–9H, and the fill limits in Rule 12-910 and Table 8. Provincial adoption and amendments vary; confirm the edition adopted locally.
How we calculated this
The fill rules, in plain English
Conductors need free space in a conduit. The CEC Rule 12-910 / Table 8 limits are: one conductor may fill 53% of the pipe's inside area, two wires 31%, and three or more 40%. We do that area math for you using the official wire and conduit dimensions.
Good to know: long runs with many bends are easier with a size larger than the legal minimum — many electricians upsize on purpose.