๐ Conduit Fill
How big a conduit do you need for your wires? Enter what you're pulling, get the smallest legal size.
Canada / CEC planning note: CEC Rule 12-910 and Table 8 use the same 53/31/40% fill percentages shown here. However, this tool still uses THHN/THWN conductor areas and NEC trade-size data because the Canadian Tables 6Aโ6K and 9 values have not passed our verification gate. Do not use its conduit-size result as the final basis for a Canadian installation; confirm it against the CEC or your inspection authority.
How we calculated this
The fill rules, in plain English
Conductors need free space in a conduit. The CEC Rule 12-910 / Table 8 limits are: one conductor may fill 53% of the pipe's inside area, two wires 31%, and three or more 40%. We do that area math for you using the official wire and conduit dimensions.
Good to know: long runs with many bends are easier with a size larger than the calculated minimum. For Canadian work, confirm conductor areas and metric trade sizes against CEC Tables 6Aโ6K and 9 before installation.