🚇 Conduit Fill

How big a conduit do you need for your wires? Enter what you're pulling, get the smallest legal size.

EMT is the common thin-wall metal tubing. Rigid PVC is the plastic conduit option.

Wire size Quantity

RW90 conductor areas come from CSA C22.1:24 Table 6A; T90 conductor areas come from Table 6K. Select the conductor type above.

Count every insulated wire in the pipe, including the neutral and an insulated ground. Use a separate row for each size.

The fill rules, in plain English

Conductors need free space in a conduit. The CEC Rule 12-910 / Table 8 limits are: one conductor may fill 53% of the pipe's inside area, two wires 31%, and three or more 40%. We do that area math for you using the official wire and conduit dimensions.

Good to know: long runs with many bends are easier with a size larger than the legal minimum — many electricians upsize on purpose.

Want to know why you should trust this result? Read how VoltDrop checks its numbers.