📦 Box Fill

Is your junction or device box big enough? Count what's in it, get a clear fits / doesn't-fit answer.

Plastic boxes have their volume stamped inside (e.g. "18.0 CU IN") — pick Custom and type it. Metal box sizes use the standard code volumes.

Wire size in the box Quantity

Add one row for each conductor size. Most homes use 14 AWG (15 A circuits) or 12 AWG (20 A circuits).

Count every hot and neutral that enters the box — including any that pass straight through unbroken (those count too). Don't count ground wires here (next question), and don't count pigtails that start and end inside the box.

devices

Switches, receptacles/outlets, and dimmers each count as two conductor allowances. This aggregate input uses the largest conductor listed above.

Bare bond wires are not counted under CEC Rule 12-3034.

Cable clamps receive no volume allowance under the Canadian counting rule.

Why box fill matters

Cram too many wires into a box and connections get stressed, insulation gets nicked, and heat builds up. The Canadian Electrical Code (Rule 12-3034 with Table 22) assigns every insulated conductor a space allowance in millilitres, and the box must have at least that much room.

The counting rules, in plain English

Canadian counting: each insulated conductor entering the box counts once; bare bond wires and cable clamps do not count. Each device counts twice. Every pair of insulated wire connectors (marrettes) counts once, using the largest conductor connected.